Fan fault detection controller

FFD-MT02A-T


Description of FFD-MT02A-T Fan Fault Detection Controller

 

一、Summary

The FFD-MT02A-T type controller is designed for detecting the heat dissipation fan. the opening temperature and fault current can be adjusted at will to achieve the purpose of adapting to different power motors. the key components of the circuit are all imported components to ensure reliable, stable and long-time operation of the circuit. the current sampling uses 24-bit high-precision AD devices. through careful wiring and high reliable programming, the product has a high cost-performance ratio in the industry.

 

 Working principle: through temperature detection and current detection to control the fan work and real-time detection of whether the fan is working properly, it has a strong ability to judge the blocking and open circuit faults.

 

二、Main technical indicators

 

1. input operating voltage: AC220V

2. maximum operating current per channel: mA 1000

3.  Fault response time :10 s        

4.  Current resolution :1 mA

5.  Resolution :1℃                

6. Duration allowed at full load :<24 hours

7. output: relay contact (open) AC250V/5A

8. fault relay output capacity: relay contacts (one open and one closed) AC250V/3A 4 sets

9. display :4-digit digital tube,

10. Use temperature :-30--80℃

11. Relative temperature :<RH90% 

12.Insulation :>100 MΩ(DC500V)

13. Pressure resistance: AC2500V /1Min (2mA)

14. Mode of installation: card gauge (arbitrary direction)


三、Connection method and terminal function

                                接线端子示意图

Terminal Function Definition

1、  IN: controller power input interface, AC/220V;

2、 The OUT: controller connects the output interface of the cooling fan in the control cabinet, AC/220V, can connect to a fan within 100 W;

3.RELAY1-4: control cabinet cooling fan fault output passive dry contact, output relay contact for a group of open, a group of closed, easy to use;

4.TEMP T-/T : the external temperature probe input, the probe is M8 threaded installation, please install in the area that can best reflect the temperature of the machine room; the line should avoid the power line as far as possible. Probe lead length :3 meters ;(note: this probe adopts high precision waterproof temperature probe, do not change at will, lest affect test accuracy)

 

5. RELAY OUT1/OUT2: external fan controls output contacts, normally open type, contact capacity :5 A/AC250V;

 

四、Overall dimension (unit: mm)

五、Panel description

六、Parameter debugging method

1. hold down the "and "-" buttons at the same time after power on, wait for the three digital tubes to shine, release the button, that is, enter the parameter adjustment mode, the fault light lights up.

 

2. Press "SET" key to change the parameter serial number, adjust the value of the parameter according to the following table, add one for each order.

 

3. when you press the digital tube to display 8888, press the ESC" key to exit the parameter adjustment mode and store the adjusted parameters.

 

 

 First Digital Tube

 Parameter Name

 Scope of adjustment

 Default

 Remarks

1

 Current upper limit

10-999(mA)

200

2

 Current limit

10-999(mA)

100

3

 Channel 1(CH1)

 

 Fan opening temperature

10-120(℃)

40

 Internal temperature sensor

4

 Channel 2(CH2)

 

 Fan opening temperature

10-120(℃)

40

 Internal temperature sensor

5

 Overtemperature

10-120(℃)

75

 Internal and external temperature sensors

6

 Function Control Position

0x00-0xff

0x0f

The control bit function is shown below

 Total extinction

 Digital display 888

 Click ESC to exit

 

4、Function control bit meaning

 

 

Content

 Parameter Name

 Default

 Control position

 Remarks

 Fault category

Channel 1(CH1) Current Overrun Fault

1

bit0

 Channel 2(CH2) Current Overrun Fault

1

bit1

 Internal sensor overtemperature fault

1

bit2

External sensor overtemperature fault

1

bit3

External temperature sensor open circuit

0

bit4

 External temperature sensor short circuit

0

bit5

 Standby

0

bit6

 Control selection of internal and external temperature sensors for cooling fans

0

bit7

 0 internal,

 

 1 External

 

 

 Note: Fault bit means 1 fault detection allowed ,0 prohibited fault detection

5. current and temperature values display switching:

a、" SET" and "at the same time to display the current value (current display mode) of the fan in the current channel control cabinet; the current indicator lights up.

 

b、" SET"" and "-" at the same time press the ambient temperature in the current channel control cabinet (temperature display mode). The temperature indicator lights up.

 

 c、 hold down the SET" key in current display mode to display the actual voltage input from the current controller and fan in the cabinet.

 

d、 hold down the SET" key to display the external temperature value in temperature display mode (0 when no temperature sensor is connected). If the function control bit is bit7 1, the internal and external are the opposite.

6. keys "CH1" and" CH2" can switch between the two channels. The first shiny digital tube is used to display channel values.

 

 7. press the "ESC" key" to display the fault code when the fault indicator lights flicker, the fault code means as follows:

 

 Display code

 Meaning (fault bit bit must enable)

E-1

 Channel 1(CH1) Overlimit Fault

E-2

 Channel 2(CH2) Overlimit Fault

E-3

 Internal sensor overtemperature fault

E-4

External sensor overtemperature fault

E-5

 External sensor short circuit fault

E-6

 External sensor open circuit fault

 

七、Troubleshooting of common problems

 

 

 Serial number

Problem description

Solution

1

 There's no reaction

 Check power input port for AC220V voltage input

2

 CH1 current display abnormal

 Are CH1 loads connected and working properly

3

 CH2 current display abnormal

Are CH2 loads connected and working properly

4

 Abnormal internal temperature

 Internal temperature display abnormal internal temperature sensor damage

5

 Exterior temperature display abnormal

 External temperature display abnormal for external temperature sensor damage or no access, or access to the temperature sensor specifications do not match.

6

 CH1 or CH2 failure

The upper and lower limits of the current are set correctly, and the actual current exceeds the set range. CH1 and CH2 use the same setting.

7

 CH1 no fault reported, relay no output

 Failure enable bit1 set to 1

8

 CH2 no fault reported, relay no output

 Failure enable bit2 set to 1

9

 Internal temperature has been overheated

 Low internal over-temperature setting or damage to temperature sensor

10

 External temperature overtemperature fault

 External over-temperature setting too low or temperature sensor damaged

11

 Internal overheating no alarm

 Failure enable bit3 set to 1

12

 External overtemperature without alarm

 Failure enable bit4 set to 1

13

 CH1 Fan does not work

 CH1 the starting temperature is too high, the actual temperature should be higher than the set temperature fan to start cooling.

14

 CH2 Fan does not work

CH1 if the starting temperature is too high, the actual temperature should be higher than the set temperature fan to start cooling。

 

八、Precautions for use

 

 1. the maximum load current of the controller is 1 A, it can not be used for a long time, nor can the output end be short-circuited.

 2. product installation position should not be as close as possible to the heating electrical components, should be placed in the best place to reflect the temperature of the cabinet space.

 3. make sure the wiring is correct and then electrified, otherwise the circuit will be permanently damaged.

 4.Do not enter liquid or corrosive gas 4. the product to avoid abnormal or damage.

 5.turn on the voltage output 3 seconds after reaching the set temperature, turn off the output when less than 2 degrees。

                                                             

 