Seismograph series

ZK-2500RS escalator seismic detection controller (networked)


  

Introduction

 

A new seismic monitoring system is introduced to customers, and this modern detection system only needs little maintenance after installation. Because the system has many functions, only after you master it is convenient for you to operate. We also sincerely hope that you can read the manual in detail before the operation.

 

Characteristics

 

● Application of patented electronic instruments for seismic monitoring

● Easy to read and easy to program LCD interface

● Meeting: ASCE25-97,CSA B44.1,ASME A17.5 and UL508 standards

● Relay output:

● maximum load 3 amps @30 V DC or 250 V AC

often open or closed

self-locking or non-self-locking

record date, time, duration and peak value of each coordinate

   ●the specific time of each seismic wave

  

Panel

 

 

Battery switch

 

 

Battery switch is used to turn on and off the battery, if not in OFF state, in order to prolong the battery life. This switch is only used for battery control. When external power input is used, the switch is placed in a OFF state, only to disconnect the battery power supply. If the external power supply is still on, the seismograph will not be turned off. If the instrument is turned off, the external power supply should be disconnected and the switch will be placed in a OFF state.

 

 

Functional keys

 

 

 

 

The following are the functions of each key:

 

 UP     move the cursor into the next position, into the next menu, data. (Long continuous)

 

 DOWN   move the cursor into the next position, into the next menu, data -. (Long as continuous -)

 

 SET    switch between function menu and normal display, enter function menu from submenu, press reset alarm.

 

 ESC    return to the next menu and power up into normal test mode (3 minutes without operation automatically into normal test   mode).

 

 

OLED is the most direct form of feedback. The screen displays the date (year/month/day) on the upper left and status information such as System Normal,TROUBLE, or Alarm below the time (24 hours) on the upper right

 

OLED display has no angle limit and low power consumption. In any environment can be displayed normally, not limited by temperature. 

 

  Relay output port

There are two connectors on the left side of the operation panel (10 stitches). There are 3 relays, each using 3 contacts. The 2-side relay is a self-locking relay. One ALARM mode output, the other is TROUBLE mode output. If triggered, they won't change even if the power is off. RELAY CONTATCT RESET key is used to reset. The intermediate non-locking relay is also output in ALARM mode and automatically reset when exiting ALARM mode.

 

 Each relay has 3 output terminals, COMNONC. (see wiring diagram)

 

Relay reset key

The key is used to reset the self-locking relay. Pressing any key will not affect the display or turn off the alarm sound. Press ALARMTROUBLE key to reset all self-locking relays. Press the ALARM or TROUBLE to hear the crisp contact action sound if the relay is already in action without affecting the system. 

 

Remote ALARM reset input port

  Connect the switch to the port for remote reset of earthquake alarm. For example, in the control room, press the switch to turn on the alarm without local reset, easy to operate. Connect a local switch to a local ALARM RELAY CONTATCT RESET. External switch :100 Ma@12VDC.

 

 

Product wiring

 

 

 

 

Product Shape Size Chart

 

 

 

Installation

 

1. Install the box body on the load-bearing wall or connected support with a screw or shaft pin. Can be installed in one of the axes (X,Y,Z) in a horizontal or vertical direction, the position self-detection program will automatically detect its position to make it horizontal. Note: do not install on easily sloshing objects to avoid the probability of misoperation.

2. Connect the control board to the relay output port, note that each relay has 3 output terminals.

     "TROUBLE" the output terminal is activated, it indicates that there is a problem with the seismograph system and requires on-site inspection. It must be connected to the sound alarm or display alarm device in the control room or cabinet. "ALARM" is the alarm output relay action. where the self-locking relay will remain until the reset key is pressed. Another non-self-locking relay operates automatically when there is an alarm and reset automatically when the alarm condition does not exist. It should be noted that the self-locking relay may be an action state or a reset state before boot. When the power is connected, press the reset key to make it reset, and the relay will respond again  Function execution (all self-reset relays, no self-locking function).

   3. if you need to use alarm remote reset, connect the switch to the REMOTE ALARM RESET terminal. Switch requires load mA@12VDC.100

 

 Access to power.

 

  4. access with a high voltage AC power supply (120 V/60HZ or 240 V/50HZ), connect to the input of the AC-DC module.

 

  5. set the battery switch to "ON"(no this function).

 

  6. press the "ALANRM" and" TROUBLE" reset keys to ensure that all self-locking relays are in reset condition.

 

 7. set the software to the initial state.

 

7. Initial setting

 

 

Turn on external input power to make it work

 

 Show up

next:

Display indicates that the external power supply is connected, and if not, OFF is displayed

A long press UP key will appear below to select the startup system.

System initialization includes compensating for errors in tilt due to installation. If not the final installation stereotype, you can choose NO will skip the system initialization function. Perform this process after installation is complete. Perform this process before complete installation can cause false alarm.

 

 Select YES, the following display appears, select NO will not initialize the system.    

      

Note that the sensor can not have any vibration during the Sensing process to ensure accurate reading. will enter normal operation mode after calibration.

 

Function

 

   

 Different functions are selected by SET keys.

 

Press the UP key to move the cursor to the corresponding menu. Press the SET key to confirm.

 

(select menu 1. TEST)

This test function uses some basic test methods to test whether the system is working properly. There are two test methods provided. Use keys UP move cursor to YES or NO. Press the SET key to select one of the test methods.

 

 1. relay test: three output relays are in action, buzzer sends out continuous alarm sound. This function can check whether the external equipment connected to these terminals is running according to the expected logic when the relay is in action.

 

2. no relay test: buzzer sends out continuous alarm sound. This function can check whether the system is working properly and does not affect the status of the relay. It also does not affect the normal operation of the connected device.

 

 

Check (select menu 2. CHECK)

 

  The following is the information that appears for this function.

  First display as version and model.

   Press the up key

  Press the up key

  Press the up key

  

Press the up key

  

 

 

 

 

 

 This function shows some state of the system. Press the UP key to scroll to the next column.

Main Power

OFF

The external power supply is not connected or working. internal battery in supply system power.

ON

External power supply is connected or working. The internal battery is not in use.

Calibrate

Completed

System initialization has been completed.

Not

Completed

 System initialization has not been completed.

Set

Date&Time

Completed

date and time has been set.

Not

Completed

Date and time have not been set, detailed operation view settings time and date chapter.

Alarm Setting

ASCE 25-97

According to the ASCE 25-97 standard of earthquake warning equipment, the system sets early warning. Check A appendix for more information about the

 

Settings (select menu) Table3.SETUP

 

 

 

 

Setup includes the following features:

 

 ● Set Date and Time

 

 ● initialization checks

 

 ● measure current acceleration values

 

 ● seismic alarm trigger settings

 

 ● Warning Detection Time

 

 ● earthquake confirmation time

 

 ● Early Warning Level

 

 

 

Set Date and Time1.SET DATE&TIME

 

 

The following is a description of the setting date and time. Remember that the format of the date is year / month / day (for example, January 25,2018 is 02/01/25), Time is 24 hours, (For example ,06:00 a. M., 18:00 at 6 p.m.).

 

 1. select date and time function settings: use the UP key to move the cursor to the 1.SET DATE&TIME" option, and then press the SET key to select. And the date or time will flash the cursor.

 

 2. use the SET key to move the cursor to where it needs to be modified.

 

 3. use the UP key to modify the value at the previously selected position.

 

 4. repeat steps 2 and 3 where modifications are required

    5. press ESC key to save the modified data to the system clock and return to the main function menu.

 

 Initialization check.CALIBRATE

 

The sensor of the seismometer has been set to the best state before leaving the factory. This initialization check function can only be aimed at a few position angle differences that may occur during installation. And only the local seismometer fixed in a certain position after the initialization check.

 

When you need to initialize the check, use the UP key to move the cursor to "2. CALIBRATE" option, and then press the SET key to determine. LCD will show:

    

 It is important that the seismograph can not be moved or vibrated throughout the calibration process. After the check is completed, the LCD will return to the normal operation interface.

 Measurement (select submenu 3. Metering)

 

The measurement function is used to measure any external force acceleration other than gravity acceleration. these forces are decomposed into (XYZ) axial acceleration shown separately. The following legend illustrates the relationship between direction and coordinate axis. A vertical axis belt has a "^" sign. For the following columns, the Z axis is vertical.

 

The measurement function has two display modes. First one shows the acceleration in each coordinate direction (unit G); the other shows the inclination on each coordinate axis. Press the UP key for 1 second and the measurement function enters acceleration measurement mode. Press the DOWN key for 1 second and will enter angle measurement mode.

in the acceleration measurement mode, each force is described as the value of an absolute g- force (1.00 G i.e., the unit of gravity acceleration). Accurate G.0.01 If the initialization check is done when boot, each axis must now be displayed as 0.00 without any external force (Z axis is 1.00).

In the angle measurement mode, the system automatically calculates the deviation between the 3D angle of the current seismograph and the angle data after the previous initialization check. Unit for degree, accuracy 1 degree.

 

Alarm Trigger Value Settings4.Alarm Setting)

 

 This function is used to set a trigger value for the local earthquake system to enter the alarm. Here are two ways to set the ASCE25-97 standard:

 

ASCE 25-97 standard provides seismic waves with a certain frequency range and the corresponding maximum and minimum acceleration threshold for determining whether an earthquake alarm is issued. Check A appendix for more information about this standard. Because of the high accuracy of the sensor, the system can divide the alarm part of the standard into 10 secondary levels.

 

This level is compiled into 01 to 10,01 is the most sensitive level ,10 is the lowest sensitivity. The default value of 06, at the middle level, is suitable for most situations. Use the UP key to change the ASCE level, press the ESC key to save the settings and return to the main function menu.

   Early warning detection time5. Suspected Time

    

Used to adjust the detection and reset time of early warning. Adjustment S.5-30

 

Earthquake alarm confirmation time*(select submenu 6. Earthquake Time)

 

Used to adjust the detection and reset time of earthquake alarm. Adjustment S.20-100

 

Early warning level (select submenu 7. Warning)

 

This feature is used to set the trigger level of the alert. There are 12 levels (01-12) to choose from. Level 01 is the most sensitive level and level 12 is the least sensitive level

 

Function Description of Relay

 

1.ALARM self-locking relay: when the acceleration value of the X、Y、Z shaft is greater than the alarm setting level (ASCE-LEVEL), the alarm output is carried out immediately, the self-locking relay action is ALARM, the screen, buzzer and indicator lamp are also prompted to operate accordingly, and the self-reset relay is reset at the same time. The relay can only be manually reset and remotely reset.

 

2.ALARM self-reset relay: when the acceleration value of the X、Y、Z axis is greater than the warning setting level (WARNING-LEVEL), the relay enters the early warning preparation stage. if the acceleration value of the X、Y、Z axis reaches the warning value again within 15 seconds, the relay continues to, and the screen, buzzer and indicator light also prompt the operation accordingly. After the vibration disappears, the delay setting time system automatically reset the screen, buzzer and indicator light into the suspected warning state. If the acceleration value of the X、Y、Z axis does not reach the warning value again during the suspected warning time, the system exits the warning state after  Electronic reset.

 

 3.TROUBLE self-locking relay: when the sensor fails, damage or external power down after the relay action suction and make the corresponding prompt interface, the relay can only manually operate reset, not remote reset.

 

 Record (select sub-menu)(24RECORD

 

The seismic wave data on the liquid crystal are as follows:

Read the seismic data on liquid crystal as follows:

 

 

There are 16 groups of data, press UP key to read the XX group of data as follows:

 

Press the UP key to see X axis acceleration values in the 13 groups

 

Press the UP key to see Y axis acceleration values in the 13 groups

 

Click the UP button to view the acceleration duration in 13 groups

 

Press the UP key to display the end of this data view.

 

 

Backup battery

 

The backup battery uses a rechargeable battery that can be automatically charged when the main power is on. a backup battery only works when the battery switch is set to the on "ON" state.

 

Alarm Mode Flow Chart

 

 

 

Detection of suspected early warning

 When the sensor detects the vibration, the display changes to the perceived state of the suspected warning, self reset relay action,

 

           

 When the vibration stops, if the alarm is not triggered enough, the display will change to normal state, self-reset relay reset.

 

 Then turn to normal detection mode.

 

 Alert

 

As the acceleration of the vibration exceeds the preset value, the system enters the ALARM detection state. When the vibration is strong enough to meet the alarm conditions, the system will activate the response relay, buzzer issued a continuous alarm sound

 

 

When the vibration ends, the system holds all the recorded data

 A non-automatic lock ALARM relay is automatically reset and the alarm sound is converted to intermittent sound. Alarm will flash on the display.

Press the ALARM RELAY CONTACT RESET key or close the REMOTE ALARM RESET input terminal to reset the self-locking ALARM relay contact.

 

 Failure

 

 

when the system found an error during self-checking, TROUBLE flashed on the screen, the fault relay triggered, and the table below lists the possible causes of the failure.

 Information

 Description

Not Colibrated

 The sensor is not initialized. This error can be solved by initializing the check function.

System Error

Sensor communication failure, need to return to the factory maintenance.

    When the fault is relieved, the liquid crystal will automatically clear the fault display. in any case, the fault self-locking relay is reset only by pressing the TROUBLE RELAY CONTACT RESET key. Reset power is not working.

 

  

System check

The system should be checked regularly to ensure that all parts are running in a normal and orderly manner.

Function CHECK:

1. Click SET key

2. Press UP until the pointer points to Check function

3. SET press

4. press UP to monitor each item (see above CHECK function for each item's explanation. )

 TEST function detection system is also running at this time. Function TEST:

1. Click SET key

2.Press UP until the pointer points to Check function

3. Click SET key

4.Press UP to select Yes( Detect Buzzer and Relay) or No( Detect Buzzer only)

If necessary, you can use the WITH RELAYS" selection function to test, which can be detected with the connected device.

Sensor analysis and calibration

Seismic sensors do not require regular calibration. In order to ensure the optimal operation of the seismic sensor, it is suggested that the system monitoring and field test should be carried out every 4-5 years, and the detection should be carried out after each earthquake event. You can also contact local distributors for more information.

Technical parameters

Sensor :3D acceleration measurement. monitor vertical (P) and horizontal (S) acceleration.

 

Response frequency :0.5-15 Hz, software filter

 

Alarm sensitivity: set according to ASCE 25-97 standard (e.g .0.15 g@1HZ,0.30g@5HZ)

 

 Self-test: Self-test action can be performed during boot, reset and operation

 

 Power supply :120-220 V AC 50/60Hz( High voltage input of power supply module)

 

 12V AC or 12V ACV-24V DC( low voltage power input to the system)

 

 Relay load capacity :5 A@250VAC or 5 A@30VDC

 

 Operating temperature range :-25~40

 

 Relative humidity :0-99%

 

 Input :2 core lead connector for remote reset of self-locking relay

 

 Output :3-core terminal connector for ALARM self-locking relay output (NC,common,NO)

 

 3-core terminal connector for ALARM non-self-locking relay output (NC,common,NO)

 

 3-core terminal connector for TROUBLE self-locking relay output (NC,common,NO)

 

 Size: See Shape Size Chart

 Certification standards

 

 This product meets the following criteria:

 

 ASCE25-97

 

 Revision of intensity and magnitude

 

Seismic intensity measures the shaking degree caused by seismic vibration in a special area. It shows the impact of earthquakes on humans, buildings and the environment at a certain location.

 

A common Roman numeral I - XⅡ is used to distinguish the magnitudes. There are some decisive factors in the magnitude of the magnitude: the composition of the soil, the distance from the center of the earthquake, and the distance between the site of the earthquake and the surface. The magnitude is not expressed by numbers, but by the damage caused by some factors, the shock and the vibration. The information was collected by investigation after the earthquake.

 

 MAX scale revision:

 

 

An earthquake is not felt except in a special, very quiet environment.

 

 

A few people in the rest or in the high floor can feel.

 

 

What people in the house obviously feel, especially the people on the high floor. Many people didn't realize it was earthquake. The standing motorcycle vibrated slightly. The vibration resembles the passing of a truck. Not long.

 

 

During the day many people in the house, a few outside the house can feel. At night, some awake people can feel it. The plates, windows, doors, walls were vibrated, feeling like a giant truck hitting the building, and the standing motorcycle swayed obviously.

 

 

Almost everyone can feel it; many people are replaced. There are plates and windows are broken. Unstable objects turn. The pendulum may stop.

 

 

 Everyone can feel that many people are frightened. Some heavy furniture moves; a lot of dust falls. Minor damage.

 

 

 Minor damage is found in buildings with better design and construction; minor damage to ordinary better structural buildings; great damage to structures with poor building quality or design; and damage to some chimneys.

 

 

 The damage in some specially designed buildings is small; the ordinary strong buildings have great damage and partial collapse. The poor building structure is damaged greatly. Chimneys, factory viaducts, monuments, walls, etc. Heavy furniture overturned.

 

 

 The specially designed buildings were badly damaged; well-designed frames collapsed. Strong buildings are damaged and most of them collapse. The building is displaced.

 

 

Some well-built wooden structures were destroyed; most stone and frame structures were destroyed. The track bends.

 

 

Only a small number of buildings remained unbroken, the bridge was destroyed and the track was badly bent.

 

 

 All destroyed. line of sight and horizontal line are distorted. Objects fly in the air.

 

 Power supply connection

 

With built-in power conversion module can be directly connected to the AC power supply (120 V 60Hz or 240 V 50Hz).

 

Warning: electric shock is dangerous. All electrical connections must be operated by qualified electrical personnel in accordance with all applicable regulations. Failure to comply with this warning may result in property loss, personal injury or death.

 

 Connect power

 

 disconnect the high voltage power supply on the connection line

 

 Pull out the power terminal,

 

 Connect the power cord to the input port of the power module and tighten

 

 Fasten the incoming and outgoing lines to objects that are not easy to pull out to ensure that the terminals can not be pulled out at will.

 

 Appendix D:ZK-2500RS Quick Installation Guide for Seismic Sensors

 

 Fasten box to load-bearing wall or floor with 2 bolts or expansion screws

 

 Note: use the support surface for carrying walls or wall mounting. When installing, make sure the surface is horizontal and not easy to vibrate or move.

 

 Connect the lead wire by pressing line

    

Online Communication